Hitachi X200 Series Inverter Standard Specifications

 

1-/3-phase 200V class

Model X200-European Version002SFEF2004SFEF2005SFEF2007SFEF2
US Version002NFU2004NFU2007NFU2
Output RatingsApplicable motor size, 4-pole kW(HP) *1 0.2(1/4) 0.4(1/2) 0.55(3/4) 0.75(1)
Rated capacity230V 0.5 1.0 1.1 1.5
240V 0.5 1.0 1.2 1.6
Rated output current (A) *2 1.4 2.6 3.0 4.0
Overloadcapacity (output current) 150% for 60 sec.
Rated output voltage (V) 3-phase (3-wire) 200 to 240V (corresponding to input voltage)
Input RatingRated input voltage (V) SFEF: 1-phase 200 to 240V+10%, -15%, 50/60Hz±5%
NFU: 1-/3-phase 200 to 240V+10%, -15%, 50/60Hz±5%
LFU: 3-phase 200 to 240V+10%, -15%, 50/60Hz±5%
Enclosure *4 IP20
Cooling method Self-cooling
Integrated EMC filter-SFEF EN61800-3 category C1 filter
-NFU/LFU
Weight (kg)-SFEF 0.8 1.0 1.5 1.5
-NFU/LFU 0.8 0.9 1.5
Model X200-European Version011SFEF2015SFEF2022SFEF2
US Version015NFU2022NFU2037LFU2055LFU2075LFU2
Output RatingsApplicable motor size, 4-pole kW(HP) *1 1.1(1.5) 1.5 (2) 2.2(3) 3.7(5) 5.5(7.5) 7.5(10)
Rated capacity230V 1.9 2.8 3.9 6.3 9.6 12.7
240V 2.0 2.9 4.1 6.6 9.9 13.3
Rated output current (A) *2 5.0 7.1 10.0 15.9 24.0 32.0
Overloadcapacity (output current) 150% for 60 sec.
Rated output voltage (V) 3-phase (3-wire) 200 to 240V (corresponding to input voltage)
Input RatingRated input voltage (V) SFEF: 1-phase 200 to 240V+10%, -15%, 50/60Hz±5%
NFU: 1-/3-phase 200 to 240V+10%, -15%, 50/60Hz±5%
LFU: 3-phase 200 to 240V+10%, -15%, 50/60Hz±5%
Enclosure *4 IP20
Cooling method Force ventilation
Integrated EMC filter-SFEF EN61800-3 category C1 filter
-NFU/LFU
Weight (kg)-SFEF 2.4 2.4 2.5
-NFU/LFU 2.3 2.4 2.3 4.2 4.2

3-phase 400V class

Model X200-European Version004HFEF2007HFEF2015HFEF2022HFEF2030HFEF2040HFEF2055HFEF2075HFEF2
US Version004HFU2007HFU2015HFU2022HFU2040HFU2055HFU2075HFU2
Output RatingsApplicable motor size, 4-pole kW(HP) *1 0.4(1/2) 0.75(1) 1.5 (2) 2.2(3) 3(4) 4(5) 5.5(7.5) 7.5(10)
Rated capacity400V 1.0 1.7 2.6 3.8 5.4 5.9 9.0 11.1
480V 1.2 2.0 3.1 4.5 6.4 7.1 10.8 13.3
Rated output current (A) *2 1.5 2.5 3.8 5.5 7.8 8.6 13.0 16.0
Overload capacity (output current) 150% for 60 sec.
Rated output voltage (V) 3-phase (3-wire) 380 to 480V (corresponding to input voltage)
Input RatingRated input voltage (V) 3-phase 380 to 480V +10%, -15%, 50/60Hz±5%
Enclosure *4 IP20
Cooling method Self-cooling Force ventilation
Integrated EMC filter-HFEF EN61800-3 category C2 filter
-HFU
Weight (kg)-HFEF 1.5 2.3 2.4 2.4 2.4 2.4 4.2 4.2
-HFU 1.4 2.2 2.3 2.3 2.3 4.2 4.2

General Specifications

ControlControl method Line-to-line sine wave pulse-width modulation (PWM) control
Output frequency range *5 0.5 to 400Hz
Frequency accuracy *6 Digital command :±0.01%, Analog command±0.4% (25 ±10°C)
Frequency setting resolution Digital: 0.1Hz, Analog: (max frequency)/1000
Voltage/Frequency Characteristic V/f control, V/f variable (constant torque, reduced torque)
Acceleration/deceleration time 0.01 to 3000 sec. (linear, sigmoid), two-stage accel./decel.
Starting torque *7 100%/6Hz
Carrier frequency range 2.0 to 12kHz
Protective functions Over-current, over-voltage, under-voltage, overload, overheat, ground fault at power-on, input over-voltage, external trip, EEPROM error, CPU error, USP error, Termister error, Driver error, Emergency stop.
Input terminalSpecification 10kohm input impedance, sink/source logic selectable
Functions FW(Forward), RV(Reverse), CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run stop), EXT(External trip), USP(Unattended start protection), SFT(Software lock), T(Analog input selection), RS(Reset), PTC(Thermistor input) *8, STA(3-wire start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID On/Off), PIDC(PID reset), UP/DWN(Remote-controlled accel./decel.) , UDC(Remote-controlled data clearing), OPE(Operator control), ADD(ADD frequency enable), FTM(force terminal mode), RDY(quick start enable), S-ST(Special-Set 2nd Motor Data), EMR(Emergency stop), NO(Not selected)
Output signalIntelligent output terminalSpecification 27V DC 50mA max open collector output, 1 terminals
1c output 250V AC/30V DC 2.5A relay (AL0, AL1, AL2 terminals)
Function RUN(run signal), FA1(Frequency arrival type 1 - constant speed), FA2(Frequency arrival type 2 - over-frequency), OL(overload advance
notice signal), OD(Output deviation for PID control), AL(alarm signal), DC(Wire brake detect on analog input), FBV(PID Second Stage
Output), NDC(ModBus Network Detection Signal), LOG(Logic Output Function), ODC(Option Card Detection Signal), LOC(Low load)
Analog output terminalSpecification 0 to 10V DC
Function Analog Frequency monitor, analog current monitor
OperatorDisplaySpecification 4-digits 7 segment LEDs
Function Parameter setting, output frequency, output current, scaled value of output frequency, trip history, I/O terminal condition, output
voltage. Rotation direction, PID Feedback, RON time, Power-on time.
Status LED Interface Power, Alarm, Run, Prg, Hz and A
Potentiometer, RUN, STOP/RESET, UP, DOWN, FUN and STR keys
OperationFrequency settingOperator keypad Up and Down keys / Value settings or analog setting via potentiometer on operator keypad
External signal 0 to 10 V DC, 4 to 20 mA
Serial port RS485 interface (Modbus RTU)
FW/RV RunOperator Keypad Run key / Stop key (change FW/RV by function command)
External signal FW Run/Stop (NO contact), RV set by terminal assignment (NC/NO), 3-wire input available
Serial port RS485 interface (Modbus RTU)
EnvironmentOperating temperature −10 to 50°C(carrier derating required for aambient temperature higher than 40°C), no freezing
Storage temperature -20 to 65°C
Humidity 20 to 90% RH
Vibration 5.9mm/s2 (0.6G) 10 to 55Hz
Location Altitude 1,000 m or less, indoors (no corrosive gasses or dust)
Other functions AVR (Automatic Voltage Regulation), V/f characteristic selection, accel./decel. curve selection, frequency upper/lower limit, 16 stage multispeed, PID control, frequency jump, external frequency input bias start/end, jogging, cooling fan On/Off, trip history etc.
Coating color Blue
Options Remote operator with copy function (SRW-0EX), input/output reactors, DC reactors, radio noise filters, braking resistors, braking units, LCR
filter, communication cables (ICS-1, 3)
*1
The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using other motors, care must be taken to prevent the rated motor current (50/60 Hz) from exceeding the rated output current of the inverter.
*2
The output voltage decreases as the main supply voltage decreases (except when using the AVR function).
In any case, the output voltage cannot exceed the input power supply voltage.
*3
The braking torque via capacitive feedback is the average deceleration torque at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous regenerative braking torque. The average decel torque varies with motor loss. This value decreases when operating beyond 50 Hz. If a large regenerative torque is required, the optional regenerative braking resistor should be used.
*4
The protection method conforms to JIS C 0920(IEC60529).
*5
To operate the motor beyond 50/60 Hz, consult the motor manufacturer for the maximum allowable rotation speed.
*6
The output frequency may exceed the maximum frequency setting (A004 or A204) for automatic stabilization control.
*7
At the rated voltage when using a Hitachi standard 3-phase, 4pole motor.
*8
Only terminal 5 is assignable the PTC (thermistor) function.

Request a Quote
Enter the products you need and hit send to receive a formal quote within 24 hrs.

Contact us

Our support hotline is available 24/7.

Phone:02 8060 8750

Contact our expert support team!